Abstract
Frequency, amplitude and phase information of the grid voltage are of great importance in constructing a robust controller structure for grid connected inverter systems. This paper presents a simple and robust approach for the instantaneous estimation of positive and negative sequence voltage components under distorted voltage conditions. A second order generalized integrator (SOGI) is used to filter the distorted voltage and to generate orthogonal voltage components for each of the three phases. These filtered and orthogonal components are used for instantaneous calculation of symmetrical components. The implemented method is frequency adaptive; the method is demonstrated and compared to a conventional phase locked loop (PLL) technique with both MATLAB/Simulink simulations and experiments utilizing the dSPACE ds1103 digital controller.
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献