Abstract
AbstractSubsequent commutation failure (SCF) can be easily generated during the first commutation failure (CF) recovery process in a line-commutated converter-based high voltage direct-current system. SCF poses a significant threat to the safe and stable operation of power systems, and accurate prediction of CF is thus important. However, SCF is affected by the operating characteristics of the main circuit and the coupling effects of sequential control response in the inverter station. These are difficult to predict accurately. In this paper, a new SCF prediction method considering the control response is proposed based on the physical principle of SCF. The time sequence and switching conditions of the controllers at different stages of the first CF recovery process are described, and the corresponding equations of commutation voltage affected by different controllers are derived. The calculation method of the SCF threshold voltage is proposed, and the prediction method is established. Simulations show that the proposed method can predict SCF accurately and provide useful tools to suppress SCF.
Funder
National Natural Science Foundation of China
Publisher
Institute of Electrical and Electronics Engineers (IEEE)
Subject
Electrical and Electronic Engineering,Energy Engineering and Power Technology,Safety, Risk, Reliability and Quality
Reference27 articles.
1. Zhao, Y., Ma, J., Jiang, T., et al. (2021). Commutation failure prediction method based on characteristic of accumulated energy in inverter. International Journal of Electrical Power and Energy Systems, 133, 141–149.
2. Mohan, M. (2021). A comprehensive review of DC fault protection methods in HVDC transmission systems. Protection and Control of Modern Power Systems, 6(1), 1–20.
3. Liu, L., Lin, S., Liu, J., et al. (2020). Analysis and prevention of subsequent commutation failures caused by improper inverter control interactions in HVDC systems. IEEE Transactions on Power Delivery, 35(6), 2841–2852.
4. Rahimi, E., Gole, A. M., Davies, J. B., Fernando, I. T., & Kent, K. L. (2011). Commutation failure analysis in multi-infeed HVDC systems. IEEE Transactions on Power Delivery, 26(1), 378–384.
5. Shen, H., Huang, S., Fei, B., et al. (2016). A new method to detect commutation failure based on mathematical morphology. Transactions of China Electrotechnical Society., 31(4), 170–177.
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献