Affiliation:
1. 1 State Grid Shandong Electric Power Company Qingdao Power Supply Company , Qingdao , Shandong , , China .
Abstract
Abstract
This paper first analyzes the mechanism of transmission line dancing and constructs the mathematical model of transmission line dancing and the parameters of transmission line dancing. Then, a transmission line dancing monitoring and warning system is designed by integrating multiple inertial sensors, and the tower monitoring main splitter and wireless inertial monitoring and warning unit are designed, respectively. Then, the transmission line dancing trajectory was denoised using the wavelet threshold method, and the two-way inequality was determined by the attitude decomposition algorithm so as to design the transmission line dancing trajectory parameter identification algorithm. Finally, the designed system is tested experimentally, and the monitoring performance of the dance monitoring trajectory system is analyzed using collected data. The results show that the angular error of the sensor’s pitch and roll attitudes is within 0.5°, the angular error of the heading angle is within 1°, and the acceleration of the smoothed signal is in the range of -0.2/g~0.2/g. The relative error of amplitude recognition is up to 2.6 cm, and the frequency recognition basically agrees with the actual movement frequency, which is 0.21 Hz, and the error of the recognized frequency is within 0.03 Hz. Hz.
Subject
Applied Mathematics,Engineering (miscellaneous),Modeling and Simulation,General Computer Science
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献