Affiliation:
1. High-Voltage Laboratory , Swiss Federal Institute of Technology Zurich (ETHZ) , Zurich , Switzerland
Abstract
Abstract
In recent years, significant achievements have been made with respect to the development of SF6-free gas insulated substations (GIS). In parallel, the interest in installing SF6-free GIS by utilities increased steadily and tenders for new substations or upgrades, which regularly also include alternative technologies. The excellent performance of SF6 was unequivocally accepted by all vendors and users so that the community became used to single technology solutions. This is no longer the case with alternative gas mixtures, and multiple technological solutions are available. However, from the present body of literature it is not possible to make a full and comparative evaluation of different alternative gas switchgear, i.e. circuit-breakers and disconnectors. Thus, the High-Voltage Laboratory of ETH Zürich started investigations and measurements of basic experiments that allow an unbiased comparison of properties of alternative gas mixtures relevant for switching. The two main purposes of these investigations are to define a set of measurements that allow an estimation and comparison of switching performance with different gas mixtures, independent of a specific interruption nozzle geometry, drive system, electrostatic design, and other design specific features, and to perform (some of) these measurements comparing pure SF6, with air, pure CO2, CO2/O2 mixture, and further specific gas mixtures that are currently proposed by manufacturers for SF6 replacement. The basic analysis behind the definition of measurements will be given in detail and the design principles of the chosen test devices and the derived test currents and diagnostics will be introduced. Test results themselves will not be given, rather they will be the subject of separate future publications.
Reference14 articles.
1. [1] M. Seeger, et al., Recent development of alternative gases to SF6 for switching applications, Cigre Reference Paper 291, 2017. https://e-cigre.org/publication/RP_291_1-recent-development-of-alternative-gases-to-sf6-for-switching-applications
2. [2] P.C. Stoller, C.B. Doiron, D. Tehlar, P. Simka, N. Ranjan: Mixtures of CO2 and C5F10O Perfluoroketone for High Voltage Applications, IEEE Trans. on Dielectrics and Electrical Insulation 24(5), 2712-2721, 201710.1109/TDEI.2017.006383
3. [3] S. Silvant, et al: Detailed analysis of live tanks and GIS circuit breakers using a new environmental friendly gas, Proceedings of the Cigre Session, A3-114 (2016)
4. [4] http://currentzeroclub.org/gas-circle/
5. [5] A. Ritter and C. M. Franck: Prediction of Bus-Transfer Switching in Future HVdc Substations, IEEE Transactions on Power Delivery 33(3), 1388-1397, 201810.1109/TPWRD.2017.2764386
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献