New control scheme for synchronizationof a photovoltaic system to a three-phase grid to attenuate the harmonics of currents caused by distorted grid voltage
-
Published:2020-12-01
Issue:3
Volume:9
Page:256
-
ISSN:2722-2624
-
Container-title:International Journal of Applied Power Engineering (IJAPE)
-
language:
-
Short-container-title:IJAPE
Author:
Boukhechem Ismail,Boukadoum Ahcen,Boukelkoul Lahcene,Medouce Houssam Eddine,Lebied Rima
Abstract
<div data-canvas-width="397.43840959483975">This study presents a new scheme of control for the synchronization of a photovoltaic (PV) system with a three-phase grid without a line sensor. The approach of the proposed synchronization technique is developed to extract the</div><div>maximum of PV energy and inject it in the network for various conditions of voltage, and to ensure that the currents injected into the three-phase network emulate the wished sinusoidal forms even when the mains grid voltage is no longer ideal. This paper in troduces a new technique of synchronization and elimination of the disturbances created by the distorted tension based on the direct power control without voltage sensors (VF_DPC) with the help of second-order generalized integrator (SOGI) associated with a self-tuning filter(STF) to extract the fundamental virtual flux. The simulation of the proposed system is realized in MATLAB/Simulink environment.</div>
Publisher
Institute of Advanced Engineering and Science
Cited by
1 articles.
订阅此论文施引文献