Author:
Abd Rahman Farah Asyikin,M Izadi,M.Z.A. Ab Kadir,J Jasni
Abstract
This paper presents a study about electric field behaviour of 10kV polymer insulator with moss deposition under foggy condition. The aim of this simulation experiment was to determine if this field affect the initiation of pollution flashover. To study this effect, simulations were carried out using High Frequency Structure Simulator (HFSS). The simulation experiment includes the results of electric field distribution along the insulator and also the magnitude of electric field at three different locations in identifying the parts of the insulator’s surface that likely to initiate pollution flashover. The moss deposited polymer insulator displayed uniformed and considerably intense distribution of electric field with the clean insulator. The field result showed the likelihood in discharging a corona effect. In short, the results indicated that electric field along the insulator surface would likely be influenced by moss deposition and foggy air.
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献