Author:
Zhang Pengju,Cong Chaonan,Tao Jiancheng,Qiu Xiaojun
Abstract
AbstractTransformer noise is dominated by low frequency components, which are hard to be controlled with traditional noise control approaches. The shunt loudspeaker consisting of a closed-box loudspeaker and a shunt circuit has been proposed as an effective sound absorber by storing and dissipating the electrical energy converted from the incident sound. In this paper, an array of shunt loudspeakers is proposed to control the 100 Hz and 200 Hz components of transformer noise. The prototype under tests has a thickness of 11.8 cm, which is only 1/28 of the wavelength of 100 Hz. The sound absorption performance of the array under random incidence is analyzed with the parallel impedance method, and the arrangement of array elements is optimized. The test results in a reverberation room show that the proposed array has sound absorption coefficients of 1.04 and 0.93 at 100 Hz and 200 Hz, respectively, which provides potential of applying this type of thin absorbers for low-frequency sound control.
Publisher
Springer Science and Business Media LLC
Cited by
6 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献