Author:
Wang Sihao,Zhou Yongrong,Ma Zhaoxing
Abstract
AbstractHigh voltage circuit breakers are one of the core equipment in power system operation, and the voiceprint signals generated during operation contain extremely rich information. This paper proposes a fault identification method for high voltage circuit breakers based on voiceprint information data. Firstly, based on the developed voiceprint information data acquisition device, the voiceprint information of a certain high voltage circuit breaker is obtained; Secondly, an improved S-transform is proposed in the article, which generates an amplitude matrix based on the S-transform of voiceprint information; Then, through the matrix Singular value decomposition method, the fault feature quantity of voiceprint information is extracted from the time–frequency angle, and the diagnosis system of the support vector machine model is established, and the system is trained to realize the fault identification of the high-voltage circuit breaker; Finally, through experimental simulation calculations, it was shown that the accuracy of the proposed fault identification method in different operating conditions reached 92.6%, verifying the good accuracy and robustness of the proposed method and equipment.
Funder
Operational Control of State Grid Electric Power Research Institute Co., Ltd
National Natural Science Foundation of China
the Natural Science Foundation of Shandong Province
Publisher
Springer Science and Business Media LLC
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献