Author:
Chen Hui,Wang Junjia,Hu Hejun,Huang Yiyun
Abstract
AbstractTo study the influence of the voltage total harmonic distortion (THDV) and its spectrum on the harmonic loss factor (FHL) and the maximum allowable load capacity ratio (Imax (pu)) for the transformer of the LHCD system, we use MATLAB software to model the LHCD system and study the winding loss and maximum allowed load capacity of the LHCD system transformer when the supply voltage source is sinusoidal and non-sinusoidal, respectively. The calculation is carried out by the method of IEEE standard C57.110 and the method of considering the skin effect. The calculation results of both methods clearly show that the THDV value of the supply voltage has a significant effect on the harmonic dissipation factor (FHL) and the maximum allowable load capacity ratio (Imax (pu)) of the transformer. And the calculation method considering the skin effect increases the maximum allowable load capacity ratio of the LHCD system transformer by about 2%. The research results have important reference value for the future retrofit design of LHCD system transformers.
Funder
The Comprehensive Research Facility for Fusion Technology Program of China under Contract
Hefei Institutes of Physical Science Fund, Chinese Academy of Sciences
Publisher
Springer Science and Business Media LLC
Reference24 articles.
1. W an, Y. X., Wang, P. D., Li, J. G., Gao, D. M., Wu, S. T. & EAST Team. Progress of the EAST project in China. In 21th International Atomic Energy Agency (IAEA) Fusion Energy Conference FT/3-3 1–8 (2004).
2. Yiyun, H. Design and experimental results of feedback control of Ohmic-heating transformer magnetic flux by LHCD power in HT-7 Tokamak. Fusion Eng. Des. 81, 2085–2091 (2006).
3. Hao, X. & Huang, Y. Y. The design of high voltage DC power supply of 4.6 GHz/500 MW LHCD. Appl. Mech. Mater. 135, 1027–1036 (2011).
4. Li, J. & Liu, F. Electromagnetic disruption analysis of 2.45 GHz LHW antenna in EAST under different plasma configurations. Fusion Eng. Des. 86, 214–219 (2011).
5. Hao, X. & Huang, Y. Y. The design of high voltage DC power supply of 4.6 GHZ/500 MW LHCD. Appl. Mech. Mater. 135–136, 1027–1036 (2012).