Affiliation:
1. Federal Nuclear Center of Russia – All-Russia Research Institute of Experimental Physics
2. Togliatti State University
Abstract
This article represents results of simulation of geomagnetically induced current impact on Consolidated power system of Centre of Russia during strong magnetic storm. The paper shows that complex of factors appears during this impact which can induce progress of blackout: significant decrease of voltage on a set of electrical power elements, mass cutoff of power transmission lines under the influence of relay protection and dangerous heating of construction elements of power transformers.
Publisher
The Russian Academy of Sciences