Author:
Ansyori Ansyori,Yani Irsyadi,Rahman Eric
Abstract
Isolation is a separator between conductors in electrical equipment that prevents flashover, resulting in a short circuit or electrical failure. Isolation is critical in electrical appliances, exceptionally High Voltage Power Equipment (HVPE), to ensure the safety of circuit breakers, capacitors, and transformers. In addition to being an isolator, the insulating liquid material also serves to cool the heat generated by electrical appliances. Isolator with mineral oil-based transformer has various environmental issues, including non-biodegradability, non-renewability, and rarity. Because it is environmentally safe and extensively used, virgin coconut oil (VCO) is an alternative transformer oil insulation. This study aims to determine the properties of Virgin Coconut Oil (VCO) breakdown voltage using the IEC 156 standard and oil temperature conditioning. According to the test results, the oil breakdown voltage before heating (at room temperature) is 14 kV, which is much below the IEC 156 standard, and the breakdown voltage after heating at 90 ° is 35 kV, and 110 ° is 40 kV, which is even higher than the IEC 156 requirement
Publisher
Asosiasi Peneliti Sriwijaya
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献