Affiliation:
1. Belarusian National Technical University
Abstract
The methods used in the microprocessor protection of electrical equipment for forming orthogonal components of input currents ensure their reliable isolation after changing the mode followed by one or more periods of the fundamental frequency. This is due to the inertia of the functional elements, in particular, digital frequency filters, as well as the saturation of the steel magnetic cores of current transformers. To increase the speed of the selection of orthogonal components of the input currents, it is proposed to form them as equivalent ones in terms of the cosine and sine components obtained using digital Fourier filters by multiplying by the resulting coefficient. The method that has been developed for determining the specified coefficient provides compensation for the delay caused by the inertia of digital filters, as well as the saturation of the steel of magnetic cores of current transformers. The proposed method of forming orthogonal components is highly effective in the modes of strong saturation of the magnetic core with a complex input action in the presence of an aperiodic component with a large damping time constant. The evaluation of the efficiency of the proposed method was performed using a complex digital model implemented in the dynamic modeling environment MatLab-Simulink. As a result of the performed studies, it was found that in the absence of saturation of the magnetic core of current transformers, as well as in the presence of a small and medium degree of saturation, the proposed method for forming equivalent orthogonal components of input currents has dynamic properties close to the ones of those that had been previously proposed. With a strong saturation of the magnetic core of current transformers, the speed of obtaining reliable values of these components is increased by 1.5–2 times.
Publisher
Belarusian National Technical University
Subject
Energy Engineering and Power Technology,Nuclear Energy and Engineering,Renewable Energy, Sustainability and the Environment
Reference14 articles.
1. Sheyerson E. M. (2007) Digital Relay Protection. Moscow, Energoatomizdat Publ. 549 (in Russian).
2. Rumiantsev Yu. V., Romaniuk F. A., Rumiantsev V. Yu., Novash I. V. (2016) Digital Filters Implementation in Microprocessor-Based Relay Protection. Enеrgеtika. Izvestiya Vysshikh Uchebnykh Zavedenii i Energeticheskikh Ob’edinenii SNG = Energetika. Proceedings of CIS Higher Education Institutions and Power Engineering Associations, 59 (5), 397–417. https://doi.org/10.21122/1029-7448-2016-59-5-397-417 (in Russian).
3. Cosse R. E., Dunn D. G., Spiewak R. M. (2005) CT Saturation Calculations: are they Applicable in the Modern World? Part I: The Question. IEEE Transactions on Industry Applications, 43 (2), 444–452. https://doi.org/10.1109/tia.2006.890023.
4. Benmouyal G., Zocholl S. E. (2002) The Impact of High Fault Current and CT Rating Limits on Overcurrent Protection. Proceedings of the 29th Annual Western Protective Relay Conference. Spokane, WA.
5. Benmouyal G., Zocholl S. E., Guzman-Casillas A. (2004) Instantaneous Overcurrent Element for Heavily Saturated Current in a Power System. Pat. US US6757146 B2.
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献