DETECTION OF CURRENT CIRCUITS FAULT FOR DIFFERENTIAL CURRENT PROTECTION

Author:

Loman M. S.,Kachenya V. S.

Abstract

False operation of the differential current protection leads to tripping of the most important electrical power objects. Fault of current transformer’s secondary circuits is one of the most often cause of false operation of the differential current protection. Early determination of this malfunction increases the reliability of the differential current protection and reduces the number of false trips. In the present article the methods of secondary open circuit determining for the differential protection are described. Some of the methods react instantly to the malfunction of secondary current circuits, and the other part identifies fault after a certain time delay. Each of considered methods has its advantages and disadvantages. A new method for determination secondary open current circuits based on the analysis of increments of the RMS values of differential and braking currents has been proposed. In this case, increments are calculated for half the period of the industrial frequency, which provides quick fault determining. The use of the sum and the difference between the increments of the brake and differential currents makes it possible to determine the open circuits in the most sensitive way. The method can be adapted to work with any type of differential protection, including transformer protection. The evaluation of the increment of the RMS current value is performed taking into account the transient process in the Fourier filter. With the aid of a computational experiment, the error limit of such an estimate is determined. The block diagram of algorithm of determination of open circuits on the basis of the analysis of increments of the acting values of brake and differential currents is presented; the principle of its functioning is described. The parameters of operation are determined. The limits of sensitivity of the method are determined, too. The time characteristics of the algorithm have been determined by the method of computational experiment with the of the MatLab Simulink simulation environment.

Publisher

Belarusian National Technical University

Subject

Energy Engineering and Power Technology,Nuclear Energy and Engineering,Renewable Energy, Sustainability and the Environment

Reference11 articles.

1. Electrical Devices Installation Rules. 7th and 6th ?ds. (2008) Moscow, Gostorgizdat Publ. 504 (in Russian).

2. Fedoseev A. M. (1984) Relay Protection of Electric Power Systems. Moscow, Energoatomizdat Publ. 520 (in Russian).

3. Shneerson E. M. (2007) Digital Relay Protection. Moscow. Energoatomizdat Publ. 549 (in Russian).

4. Microprocessor Relay MP901, MP902 for Differential Protection of Busbars: User Manual, PShIZh 144.00.00.00.003 RE, Revision 3.00. Available at: http://bemn.by/filedownload.php?file=3131.pdf (Accessed 20 April 2017) (in Russian).

5. Tire protection device REB670. Version 2.1. Product Guide. Available at: https://library.e.abb.com/public/ac2020f4dcd54b8d802988ed68f26e1b/1MRK505340-BRU_A_ru_REB670_2.1.pdf (?cessed 28 March 2017) (in Russian).

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

1. Formation of Instantaneous Differential and Restraining Cur-rents for Differential Protection of Busbar Assemblies;ENERGETIKA. Proceedings of CIS higher education institutions and power engineering associations;2020-10-13

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3