Author:
An Yunzhu,Yin Kaiqiang,Huang Tao,Hu Yuanchao,Ma Chenghui,Yang Minghao,An Bingchen,Chen Dan
Abstract
During the long-term operation of electrical equipment, the insulation performance of applied SF6 gas may be affected by humidity, pressure, and temperature. In this study, the collision cross sections of SF6 and H2O are considered, including ionization, attachment, excitation, and elastic collision. In order to analyze the influencing factors of SF6 insulation performance, discharge parameters are computed by the Boltzmann equation under different environmental conditions, including humidity, pressure, and temperature. It is concluded that with the conditions of 0.1 MPa and 300 K, the critical breakdown electric field increases by 1.23 kV/cm as the relative humidity increases from 0% to 80%. As the pressure increases from 0.1 to 0.6 MPa, the critical breakdown electric field increases by 451.07 kV/cm. However, temperature also has little effect on the insulation performance of SF6 gas. The conclusions of this study have reference value for safe and stable operation of SF6 insulated power equipment.
Funder
National Natural Science Foundation of China
Natural Science Foundation of Shandong Province
Natural Science Foundation of Jiangsu Province
Subject
Physical and Theoretical Chemistry,General Physics and Astronomy,Mathematical Physics,Materials Science (miscellaneous),Biophysics
Reference23 articles.
1. Sulfur Hexafluoride and the Electric Power Industry[J];Christophorou;IEEE Electr. Insul. Mag.,1997
2. SF6/N2 Mixtures: Basic and HV Insulation Properties;Christophorou;IEEE Trans Dielectr Electr Insulation,2002
3. Simulation and Analysis of Electron Transport Parameters in Air Discharge;Liu;High Volt Eng,2011
4. Electron Swarm Development in SF6. I. Boltzmann Equation Analysis;Itoh;J. Phys. D Appl. Phys.,1988
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献