Author:
Mao Chizu,Liu Xianchao,Li Qing,Xu Zhihua,Xin Yechun,Wang Tuo
Abstract
Continuous commutation failure is very likely to occur in the hybrid Multi-infeed high-voltage direct current (HMIDC) after AC failure. In order to improve the recovery quality after HMIDC failure, an AC-DC voltage-dependent current order limiter (VDCOL) based on system strength index is proposed in this article. Firstly, the control mode transition process and system recovery process after DC failure are analyzed based on the hybrid multi-infeed DC transmission port model. Then, considering the impact of AC voltage and DC voltage input signals of VDCOL on AC voltage recovery and DC power recovery, respectively, the interaction factor and strength index of the hybrid multi-infeed system are constructed. Moreover, the weight coefficient of AC and DC voltage is calculated according to the strength of the multi-infeed system. Finally, a three-infeed hybrid DC transmission simulation model is built in the MATLAB/Simulink digital simulation platform. The simulation results demonstrate that the rapid recovery strategy proposed in this article can effectively suppress continuous commutation failure and improve the recovery speed of AC voltage and DC power.
Funder
China Southern Power Grid
Subject
Economics and Econometrics,Energy Engineering and Power Technology,Fuel Technology,Renewable Energy, Sustainability and the Environment
Reference21 articles.
1. Review of hybrid multilevel converter topologies utilizing thyristors for HVDC applications.;Bakas;IEEE Transactions on Power Electronics,2020
2. Analysis of voltage and power interactions in multi-infeed HVDC systems.;Denis;IEEE Transactions on Power Delivery,2013
3. Analysis and improvement of the multiple controller interaction in LCC-HVDC for mitigating repetitive commutation Failure.;Hong;IEEE Transactions on Power Delivery
4. Analysis and improvement of the multiple controller interaction in LCC-HVDC for mitigating repetitive commutation Failure.;Hong;IEEE Transactions on Power Delivery
5. Review on optimization control strategy for voltage dependent current order limiter.;Huang;Guangdong Electric Power,2018
Cited by
2 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献