Abstract
As a key state parameter of high-voltage cables, conductor temperature is an essential determinant of the current carrying capacity of cables, but in practice, this is difficult to measure directly during the operation of high-voltage cables. In this paper, the electromagnetic-thermal coupling analysis model of a 110 kV high-voltage cable is established using the finite element analysis software COMSOL. By analyzing the temperature distribution law of high-voltage cables under different load currents and ambient temperatures, the relationship between the change in the high-voltage cable surface temperature and the conductor temperature is deduced, which allows the monitoring of the high-voltage cable conductor temperature. Taking the 110 kV cable of the Yanzhong line in Shanxi Province as an example and using the electromagnetic-thermal coupling temperature field analysis method, the conductor temperature of the high-voltage cable can be measured using the data obtained from the cable surface temperature, which is measured by the self-developed Raman Distributed Temperature Sensor (RDTS) system with a maximum measurement error of about 2 °C. The method is easy to use and can achieve the accurate measurement of the conductor temperature without damaging the cable body.
Funder
National Natural Science Foundation of China
Patent Promotion and Exploitation Program of Shanxi Province
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献