Investigating Aging Characteristics of Oil-Immersed Power Transformers’ Insulation in Electrical–Thermal–Mechanical Combined Conditions

Author:

Yuan Zonghui12,Wang Qian2,Ren Zhigang2,Lv Fangcheng1,Xie Qin1,Geng Jianghai1,Zhu Jianhao1,Teng Fuyun1

Affiliation:

1. Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense, North China Electric Power University, Baoding 071003, China

2. Electric Power Research Institute of State Grid Beijing Electric Power Co., Ltd., Beijing 100075, China

Abstract

The condition and health of large oil-immersed power transformers’ insulation have a direct impact on the safety and stability of the power grid. Therefore, it is crucial to investigate the aging characteristics of oil–paper insulation in power transformers. In this study, we developed a computational model for reclosing current calculation and multiphysics coupling models for magnetic-circuit-force, electrostatic field, and temperature field simulations. The calculated aging resulted in a mechanical stress of 8.71 MPa, an electric field strength of 2.26 × 106 V/m, and a temperature of 113.7 °C. We conducted combined electrical–thermal–mechanical aging tests on the oil–paper insulation and measured various insulating paper performance parameters at different aging stages. Our study revealed that both the mechanical and electrical properties of the insulating paper deteriorated in both aging groups. However, the changes were more pronounced in the electrical–thermal–mechanical aging group compared to the electrical–thermal aging group, indicating that mechanical stress accelerated the aging process of the insulating paper. In the early stages of aging, the rate of performance changes in the electrical–thermal aging group was similar to that in the electrical–thermal–mechanical aging group. However, as the aging time increased, the degradation of performance induced by mechanical aging became more significant. This suggests that the insulating paper’s resistance to mechanical damage, specifically short-circuit resistance, noticeably decreased after prolonged aging.

Funder

Science and Technology Project of State Grid Beijing Electric Power

Publisher

MDPI AG

Subject

Polymers and Plastics,General Chemistry

Reference30 articles.

1. Huang, M. (2018). Study on Aging Characteristics of Oil-Paper Insulation under Combined Electrical and Thermal Stresses. [Master’s Thesis, Fuzhou University].

2. Reviews on oil-paper insulation thermal aging in power transformers;Liao;Trans. China Electrotech. Soc.,2012

3. Effect of mineral oil and vegetable oil on thermal ageing characteristics of insulating paper;Liu;Insul. Mater.,2020

4. Study on decreasing law of degree of polymerization of cellulose insulating paper with accelerated thermal aging;Wei;Synth. Mater. Aging Appl.,2019

5. Kunakorn, A., Pramualsingha, S., Yutthagowith, P., Nimsanong, P., and Kittiratsatcha, S. (2023). Accurate assessment of moisture content and degree of polymerization in power transformers via dielectric response sensing. Sensors, 23.