Abstract
The demand for district heating and cooling systems in block units with a heat pump that utilizes various unused energy sources for energy supply has been increasing. This study investigated experimentally the ground source heat pump (GSHP) and sewage water source heat pump (SWSHP) facilities used in block cooling and heating networks. Then, a heat pump performance prediction model was derived for utilization in future designs. Operational data for heating and cooling energy supply from an experimental site were investigated for the period between 2018 and 2020. During the cooling season, the coefficient of performance (COP) of the GSHP was approximately 4.1, and that of the SWSHP was approximately 2.9. The cooling performance of the SWSHP gradually decreased because of the fouling. The COP of the GSHP and SWSHP during the heating season was approximately 3.6 and 3.4, respectively. The results also demonstrated that, if fouling in the SWSHP can be prevented or reduced, the acquired COP can be similar to that of the GSHP. The derived prediction model serves as a good reference for engineers who require information on the performance of field operations.
Funder
Korea Institute of Energy Technology Evaluation and Planning
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
5 articles.
订阅此论文施引文献