Abstract
When detecting the presence of partial discharge (PD) activity in the insulation system in high-voltage equipment, the excitation voltages at variable frequency have been widely used instead of power-frequency (50/60 Hz) sinusoidal voltage in order to reduce the charging power. This work reviews the relevant research on PD activity at very low frequency (VLF) method, including sinusoidal or cosine-rectangular voltage shape, and damped AC (DAC) method. Based on the research history and development status, some major PD characteristics, such as PD inception voltage (PDIV), PD amplitude, PD charge, PD phase-resolved pattern, and several hot issues, such as surface charge decay and statistical time lag, have been discussed. Moreover, the advantages, disadvantages, and applied conditions of two reviewed methods has been summarized. Finally, the prospects have been made on the main development trends of this research field in the future.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Reference118 articles.
1. Partial Discharge in Electrical Power Apparatus;König,1993
2. IEEE. Guide for Field Testing and Evaluation of the Insulation of Shielded Power Cable Systems Rated 5 kV and Above,2012
3. IEEE. Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment,2007
4. Effect of supply voltage frequency on testing of insulation system