Abstract
This article (case study) discusses the influence of household photovoltaic generation on the voltage quality in a three-phase 0.4 kV grid. The research analyzes remotely acquired data from two specially designed three-phase Y-connected power meters to understand the PV system’s influence on the grid. The values of the voltages, currents, THD, individual harmonics, power factor, and K-factor are obtained every 200 ms over several months, creating more than 20 GB of data. The loads are typical household electrical appliances and EV portable chargers. The main conclusion after analyzing the measurements is that three-phase PV generation in the presence of household loads can create or increase grid unbalance; important current values into the neutral wire and THD and K-factor increase in some cases. The results also uncovered that without current sensing at the household connection point to the three-phase grid to control the PV inverter, the balanced phase output power of the grid-tied inverter is harmful to the 0.4 kV grid balance.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference17 articles.
1. IEA (2023, March 01). Evolution of Annual Solar PV Installations and Share by Segmentation, 2000–2021. Available online: https://www.iea.org/data-and-statistics/charts/evolution-of-annual-solar-pv-installations-and-share-by-segmentation-2000-2021.
2. Gao, X., Wang, Y., Wang, Z., and Yang, Z. (2019, January 21–23). A Method of Solving Three-Phase Power Unbalance Problem with PV Inverters Connected to the Grid in Series. Proceedings of the 2019 4th International Conference on Power and Renewable Energy (ICPRE), Chengdu, China.
3. Review of three-phase inverters control for unbalanced load compensation;Raef;Int. J. Power Electron. Drive Syst. (IJPEDS),2019
4. Lucas, A. (2018). Single-Phase PV Power Injection Limit due to Voltage Unbalances Applied to an Urban Reference Network Using Real-Time Simulation. Appl. Sci., 8.
5. Hossain, M.S., Abboodi Madlool, N., Al-Fatlawi, A.W., and El Haj Assad, M. (2023). High Penetration of Solar Photovoltaic Structure on the Grid System Disruption: An Overview of Technology Advancement. Sustainability, 15.