Investigation on Pollution-Induced Flashovers of In-Service Insulators in Ethiopian Power Transmission Lines

Author:

Desta Berhanu Zelalem12,Wogari Mengesha M.2,Gubanski Stanislaw M.3ORCID

Affiliation:

1. Faculty of Electrical and Computer Engineering, Bahir Dar Institute of Technology, Bahir Dar University, Bahir Dar P.O. Box 26, Ethiopia

2. School of Electrical and Computer Engineering, Addis Ababa Institute of Technology, Addis Ababa University, Addis Ababa P.O. Box 385, Ethiopia

3. Department of Electrical Engineering, Chalmers University of Technology, 412 96 Gothenburg, Sweden

Abstract

Power transmission lines in Ethiopia are experiencing an alarmingly high frequency of unexplained outages triggered by environmental factors, which significantly undermine the reliability of the country’s power system. This paper presents investigations aiming to identify those among the unexplained fault records that have been caused by pollution induced flashovers. An identification method is developed, which associates the contextual fault features, such as information about the characteristics of the fault, fault location, and time of day, as well as month of its occurrence with local meteorological/climatic and environmental conditions. A total number of 4231 unexplained faults, recorded between 2015 and 2022, were analyzed. Among them, 1045 faults (24.7%) were identified as being most likely caused by pollution induced flashovers. The entire network suffered from more than 130 pollution-induced flashovers annually with a frequency of about 0.8 faults/100 km/year. The fault frequency strongly differed among the grid regions, being highest in the Northeast and lowest in the Southwest region. Moreover, the performed analyses also concentrated on the evaluation of the pollution performance of various insulator types employed in the network. The results indicate that porcelain insulators have the highest pollution-induced flashover intensity of 1.47 faults/year/1000 units, followed by silicone rubber polymeric composite insulators and glass insulators with the respective intensities of 1.21 and 0.83 faults/year/1000 units. These results indicate that despite the high expectations towards the pollution performance of silicone rubber polymeric insulators, their use in the Ethiopian climatic and environmental conditions appears to be unsatisfactory.

Funder

Swedish International Development Cooperation Agency (Sida)—Ethiopia Bilateral Program

Publisher

MDPI AG

Reference30 articles.

1. CIGRE Taskforce 33.04.01 (2000). Polluted Insulators: A Review of Current Knowledge, CIGRE. CIGRE Technical Publication 158.

2. Macey, R., Vosloo, W., and de Tourreil, C. (2004). The Practical Guide to Outdoor High Voltage Insulators, Crown Publications.

3. Ethiopian Electric Power EEP Operational and Fault Data from 2015 to 2022.

4. Analyses of Unexplained Faults in Transmission Lines in the Power Grid of Ethiopia;Berhanu;Electr. Power Syst. Res.,2024

5. Major, M. (1993). Investigation of Contamination Flashover as a Possible Cause for Unexplained Faults on the Montana Power Company’s 500 kV Transmission Lines. [Master’s Thesis, Montana St. University].