Evaluation of Heated Window System to Enhance Indoor Thermal Comfort and Reduce Heating Demands Based on Simulation Analysis in South Korea

Author:

Lee Hyomun1ORCID,Lee Kyungwoo2,Kang Eunho1,Kim Dongsu1ORCID,Oh Myunghwan3,Yoon Jongho1

Affiliation:

1. Department of Architectural Engineering, Hanbat National University, Daejeon 34158, Republic of Korea

2. Sustainable Design Team of R & D Center, Junglim Architecture, Seoul 04526, Republic of Korea

3. Center for Climatic Environment Real-Scale Testing, Energy Division, Korea Conformity Laboratories, Seosan 31900, Republic of Korea

Abstract

Heated glass can be applied to improve windows’ condensation resistance and indoor thermal comfort in buildings. Although this applied technology has advantages, there are still some concerns in practical applications, such as additional energy consumption and control issues. This study evaluates the effectiveness of a heated window heating (HWH) system in terms of thermal comfort and heating energy performance (HEP). The simulation-based analysis is performed to evaluate the effectiveness of the HWH using a residential building model and to compare it with radiant floor heating (RFH) and hybrid heating (HH) systems (i.e., combined HWH and RFH). This study also investigates the peak and cumulative heating loads using HWH systems with various scenarios of control methods and setpoint temperature. The predicted mean vote (PMV) is used as an indoor thermal comfort index. The ratio of cumulative thermal comfort time to the entire heating period is calculated. The results show that HWH and HH can reduce the heating load by up to 65.60% and 50.95%, respectively, compared to RFH. In addition, the times of thermal comfort can be increased by 12.55% and 6.98% with HWH and HH, respectively. However, considering the social practices of South Korea, HH is more suitable than HWH. Further investigations for HH show that a surface setpoint of 26 °C is proper, considering both heating demands and thermal comfort. In addition, the setpoint temperature should be determined considering HEP and the thermal comfort for HWH, and the optimal setpoint temperature was suggested under specific conditions.

Funder

Korea Agency for Infrastructure Technology Advancemen

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction

Reference32 articles.

1. (2022, December 22). UN Environment Programme, 2022 Global Status Report for Buildings and Construction. Available online: https://www.unep.org/resources/publication/2022-global-status-report-buildings-and-construction.

2. Energy performance evaluation of a plus energy house based on operational data for two years: A case study of an all-electric plus energy house in Korea;Lee;Energy Build.,2021

3. International PASSIVE HOUSE Association (2022, December 22). Passive House Guidelines. Available online: https://passivehouse-international.org/index.php?page_id=80.

4. Impact of window selection on the energy performance of residential buildings in South Korea;Ihm;Energy Policy,2012

5. Flow patterns and thermal comfort in a room with panel, floor and wall heating;Myhren;Energy Build.,2008