Abstract
The indoor air quality (IAQ) of severely polluted toilets is associated with the transmission of diseases. Computational fluid dynamics (CFD) methods and experimental measurements were used to analyze the diffusion characteristics of pollutants. This study investigated the diffusion characteristics and normalized concentration of ammonia and hydrogen sulfide pollutants under three ventilation systems—mixing ventilation (MV), personalized ventilation (PV), and impinging jet ventilation (IJV)—in a public toilet. The mean age of air (MAA) and air exchange efficiency (AEE) were also analyzed in our study. The results show that the MV scheme has a poor removal effect on pollutants compared with PV and IJV. IJV has advantages in reducing the normalized concentration of pollutants and improving the IAQ. Increasing the number of air changes per hour (ACH) may lead to a longer MAA and reduced air exchange efficiency. Choosing an appropriate number of air changes is very important to improve the IAQ in the toilet.
Funder
National Key R&D Program Project Development and application of key technologies for rural toilets
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
6 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献