Abstract
Very fast transient overvoltage (VFTO) generated by an operating disconnector is one of the main reasons for electromagnetic disturbance in gas-insulated switchgear (GIS) substations. Generally, the amplitude of VFTO can be used as one of the references for the insulation design of GIS primary electric power equipment, so it is necessary to obtain its accurate amplitude. In this study, a new VFTO measuring sensor is developed and its measurement performance is demonstrated through hundreds of operations by a disconnector in a 220 kV GIS test circuit. The validation shows that the low cut-off frequency of the new VFTO measuring sensor has been greatly expanded to 0.01 mHz, which is improved by about 50% compared with the old sensor. The measurement accuracy of amplitude of VFTO micro-pulse improves greatly by about 80% compared with the old one. Thus, the new VFTO measuring sensor can fully meet the measurement needs of trapped charge voltage, power frequency voltage, and high-frequency transient voltage in VFTO waveform. It can be used to provide more accurate data support for insulation design of GIS primary power electric equipment in extra-high voltage (EHV) and ultra-high voltage (UHV) GIS substations.
Funder
National Natural Science Foundation of China
Subject
Electrical and Electronic Engineering,Biochemistry,Instrumentation,Atomic and Molecular Physics, and Optics,Analytical Chemistry
Reference28 articles.
1. Electromagnetic disturbances in gas-insulated substations and VFT calculations;Ametani;Electr. Power Syst. Res.,2018
2. Study on the Influence of Disconnector Characteristics on Very Fast Transient Overvoltages in 1100-kV Gas-Insulated Switchgear;Chen;IEEE Trans. Power Deliv.,2015
3. Cheng, L., He, Z., Liu, J., Yang, Z., Chen, X., Zhang, Y., Wang, S., and Si, J. (2022). Research on Radiated Disturbance to Secondary Cable Caused by Disconnector Switching Operation. Energies, 15.
4. Experimental Research on the Characteristics of Very Fast Transient Overvoltage in Ultra High Voltage Gas Insulated Switchgear;Chen;Proc. CSEE,2011
5. Study on VFTO of 1000 kV GIS Substation;Gu;High Volt. Eng.,2007
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献
1. Modeling and Analysis of VFTO Interference in Substation Isolation Switches;2023 5th International Academic Exchange Conference on Science and Technology Innovation (IAECST);2023-12-08