Thermal Performance Evaluation of a Data Center Cooling System under Fault Conditions

Author:

Cho JinkyunORCID,Park BeungyongORCID,Jeong Yongdae

Abstract

If a data center experiences a system outage or fault conditions, it becomes difficult to provide a stable and continuous information technology (IT) service. Therefore, it is critical to design and implement a backup system so that stability can be maintained even in emergency (unforeseen) situations. In this study, an actual 20 MW data center project was analyzed to evaluate the thermal performance of an IT server room during a cooling system outage under six fault conditions. In addition, a method of organizing and systematically managing operational stability and energy efficiency verification was identified for data center construction in accordance with the commissioning process. Up to a chilled water supply temperature of 17 °C and a computer room air handling unit air supply temperature of 24 °C, the temperature of the air flowing into the IT server room fell into the allowable range specified by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers standard (18–27 °C). It was possible to perform allowable operations for approximately 320 s after cooling system outage. Starting at a chilled water supply temperature of 18 °C and an air supply temperature of 25 °C, a rapid temperature increase occurred, which is a serious cause of IT equipment failure. Due to the use of cold aisle containment and designs with relatively high chilled water and air supply temperatures, there is a high possibility that a rapid temperature increase inside an IT server room will occur during a cooling system outage. Thus, the backup system must be activated within 300 s. It is essential to understand the operational characteristics of data centers and design optimal cooling systems to ensure the reliability of high-density data centers. In particular, it is necessary to consider these physical results and to perform an integrated review of the time required for emergency cooling equipment to operate as well as the backup system availability time.

Publisher

MDPI AG

Subject

Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)

Reference22 articles.

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3