Impact of the Speed of Airflow in a Cleanroom on the Degree of Air Pollution

Author:

Mičko PavolORCID,Hečko Dávid,Kapjor Andrej,Nosek RadovanORCID,Kolková ZuzanaORCID,Hrabovský Peter,Kantová Nikola ČajováORCID

Abstract

The high-energy requirements of cleanrooms are the main motivation for optimizing their operational conditions. The ventilation system consumes the most energy in order to ensure the precise air conditioning of the room (filtration, temperature, and humidity adjustment). The main function of the ventilation system is to keep particle concentration to a minimum. This work deals with the optimization of an experimental operating room via the optimization of air supply through the distribution element (laminar airflow ceiling) in the range of 0.15–0.25 m·s−1. The laminar airflow between the distribution element and the patient is influenced by the operating light and different airflow velocities. These factors affect changes in particle concentration. Ansys Fluent software was used to investigate the nature of the flow, velocity profiles, and particle trajectories. The results of our numerical simulation demonstrate that a suitable flow rate setting increases the efficiency of particle reduction in the operating table area by up to 54%, which can, in turn, reduce operating costs. The simulated air velocity profile was subsequently verified using the particle image velocimetry (PIV) method. The typical size of particles monitored for in cleanrooms is 0.5 μm according to ISO EN 7. Therefore, the results of this study should be helpful in correctly designing distribution elements for clean rooms.

Funder

Slovak Research and Development Agency

European Regional Development Fund

Publisher

MDPI AG

Subject

Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science

Reference62 articles.

1. ANNEX 1 Manufacture of Sterile Medicinal Products,2008

2. An experimental study on the influences of air change rate and free area ratio of raised-floor on cleanroom particle concentrations

3. Saving energy in cleanrooms;Fedotov;Cleanroom Technol.,2014

4. Cleanroom energy benchmarking results;Tschudi;ASHRAE Trans.,2002

5. Cleanroom energy efficiency strategies: Modeling and simulation

Cited by 10 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献