Abstract
This study aimed to determine the water demand of a municipal swimming pool complex to propose water use efficiency measures. Concomitantly, the possibility of recycling and reusing the water from filter backwashing was evaluated. The pools consumed 25.6% of water, the filter backwashing 24.5%, and the showers 34.7%. Despite the current impossibility of reducing water consumption in pools and filter backwashing, it is feasible to promote more efficient use of water through reducing water consumption by adopting simple water-saving initiatives for showers, taps, and flushing cisterns. These were organized into three distinct scenarios: (a) flushing cistern volume adjustment and the replacement of washbasin and kitchen taps; (b) flushing cistern volume adjustment and shower replacement and (c) flushing cistern volume adjustment, shower, washbasin, and kitchen taps replacement. Under scenarios 1, 2, and 3, the water consumption reduction was 8.0, 13.2, and 20.4%, respectively. The initial investment for scenario 1 was €2290.5, €859.0 for scenario 2 and €3149.5 for scenario 3; the annual water bill reduction was €7115.4, €11,518.1, and €17,655.9, respectively. Therefore, the turnover of the investment was four (scenario 1), one (scenario 2), and three months (scenario 3). The filter washings attained the required standard for irrigation after being subjected to 15 h of sedimentation.
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
6 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献