Anomaly Detection of Underground Transmission-Line through Multiscale Mask DCNN and Image Strengthening

Author:

Kim Min-Gwan1,Jeong Siheon1,Kim Seok-Tae2,Oh Ki-Yong1ORCID

Affiliation:

1. Department of Mechanical Convergence Engineering, Hanyang University, 222 Wangsimni-ro, Seondong-gu, Seoul 04763, Republic of Korea

2. KEPCO Research Institute, Korea Electric Power Corporation, 105 Munji-ro, Yuseong-gu, Daejeon 34056, Republic of Korea

Abstract

This study proposes an integrated framework to automatically detect anomalies and faults in underground transmission-line connectors (UTLCs) with thermal images because anomaly detection of underground transmission-line connectors (UTLCs) plays a critical role in power line risk management. The proposed framework features three key characteristics. First, the measured thermal images were preprocessed through z-score normalization and image strengthening. Z-score normalization improves the robustness of feature extraction for UTLCs even though noise exists in a thermal image, and image strengthening improves the accuracy of segmentation for UTLCs. Second, a preprocessed thermal image is segmented to detect UTLCs by addressing a multiscale mask deep convolutional neural network (MS mask DCNN). The MS mask DCNN effectively detects UTLCs, enabling anomaly detection only for pixels of UTLCs. Specifically, the multiscale feature extraction module enables the extraction of distinct features of UTLCs and environments, and the skip-layer fusion module concatenates distinct features from the feature extraction module. Furthermore, a half tensor is used to reduce computational resources but maintain the same segmentation accuracy, enhancing the feasibility of the proposed framework in field applications. Third, anomaly detection is performed by addressing the contour method and unsupervised clustering method of DBSCAN. The contour method compensates for the limits of the MS mask DCNN for real-world applications because the neural networks cannot secure perfect accuracy of 100% owing to a lack of sufficient training images and low computational resources. DBSCAN improves the accuracy of diagnosis and ensures robustness to eliminate noise from thermal reflection caused by low-emissivity objects. Field experiments with high-voltage UTLCs demonstrated the effectiveness of the proposed framework. Ablation studies also confirmed that the methods addressed in this study outperform other methods. The proposed framework with a novel automatic non-destructive patrol inspection system would decrease the risks of human casualties during the periodic operation and maintenance of UTLCs, which are currently the most critical concerns.

Funder

Korea Electric Power Corporation

National Fire Agency

Korea government

Publisher

MDPI AG

Subject

General Mathematics,Engineering (miscellaneous),Computer Science (miscellaneous)

Reference41 articles.

1. Aging of 154 kV underground power cable insulation under combined thermal and electrical stresses;Aras;IEEE Electr. Insul. Mag.,2007

2. Fault location for underground power cable using distributed parameter approach;Yang;IEEE Trans. Power Syst.,2008

3. Trend adjusted lifetime monitoring of underground power cable;Bicen;Electr. Power Syst. Res.,2017

4. Bascom, E.C.R., and Antonello, V.D. (2011, January 1–3). Underground power cable consideration: Alternatives to overhead. Proceedings of the Conference Minnesota Power Systems, Brooklyn Center, MN, USA.

5. Identification and location of PD defects in medium voltage underground power cables using high frequency current transformer;Shafiq;IEEE Access,2019