Predicting Contamination Spread Inside a Hospital Breakroom with Multiple Occupants Using High Fidelity Computational Fluid Dynamics Simulation on a Virtual Twin

Author:

Nagarajan Vijaisri1,Fougere Nicolas1ORCID,Schechter-Perkins Elissa M.2ORCID,Baker William E.3ORCID,Mann Adrien1,Jilesen Jonathan1,Altawil Zaid2

Affiliation:

1. Dassault Systèmes, SIMULIA, 990 N Squirrel Road, Suite 100, Auburn Hills, MI 48326, USA

2. Department of Emergency Medicine, Chobanian & Avedisian School of Medicine, 72 East Concord St, Boston, MA 02118, USA

3. Department of Emergency Medicine, University of Vermont Larner College of Medicine, UVMMC, 111 Colchester Ave, WP1—106, Burlington, VT 05401, USA

Abstract

Mitigating the rise and spread of contaminants is a major challenge faced during any contagious disease outbreak. In densely occupied areas, such as a breakroom, the risk of cross-contamination between healthy and infected individuals is significantly higher, thereby increasing the risk of further spread of infectious diseases. In this study, a high fidelity transient fluid solver and Lagrangian particle-based method were used to predict the airflow distribution and contaminant transmission inside a detailed 3D virtual twin of an emergency hospital breakroom. The solver efficiently captured the contaminants emitted simultaneously from multiple talking occupants as well as their propagation inside the breakroom. The influence of airflow distribution on the aerosol spread inside the breakroom for two different air conditioning vent positions was demonstrated with all occupants and with reduced occupants. The baseline simulation with all occupants in the breakroom showed a higher risk of contamination overall as well as between adjacent occupants. It was observed that there was a 26% reduction in the contaminants received by the occupants with the proposed modified vent arrangement and a 70% reduction with the scenarios considering a reduced number of occupants. Furthermore, the fomite deposition and cross-contamination between adjacent humans significantly changed with different ventilation layouts. Based on the simulation results, areas with higher contaminant concentrations were identified, providing information for the positioning of UV lights in the breakroom to efficiently eliminate/reduce the contaminants.

Publisher

MDPI AG

Subject

Management, Monitoring, Policy and Law,Renewable Energy, Sustainability and the Environment,Geography, Planning and Development,Building and Construction

Reference55 articles.

1. (2015). OSHA Safety and Health Program Management Guidelines: Occupational Safety and Health Administration (OSHA).

2. Center for Disease Control and Prevention (CDC) (2020). Infection Prevention and Control Recommendations for Health Care Personnel during the Coronavirus Disease 2019 (COVID-19) Pandemic.

3. (2017). Ventilation of Health Care Facilities: ANSI/ASHRAE/ASHE Addendum to ANSI/ASHRAE/ASHE (Standard No. 170-2017).

4. World Health Organization (2021, February 11). COVID-19: Health and Safety in the Workplace, Q&A. 26 June 2020. Available online: https://www.who.int/emergencies/diseases/novel-coronavirus-2019/question-and-answers-hub/q-adetail/coronavirus-disease-covid-19-health-and-safety-in-the-workplace.

5. Aerodynamic Analysis of SARS-Cov-2 in Two Wuhan Hospitals;Liu;Nature,2020