Abstract
Air conditioning loads (ACLs) are potential flexible resources that can provide various grid services to the power system. Recent studies have attempted to represent their flexibility using a virtual battery (VB) model for quantification, but the modeling process requires information on thermal parameters and heat disturbances (e.g., solar irradiation and internal heat load) that are difficult to measure. In this paper, we present a new method that models a VB without prior knowledge of such information. First, we construct a thermal dynamic model of an individual ACL using historical input-output data. The linear regression model parameters are identified without using the measurements of disturbances. Second, we derive a VB model from the linear regression parameters using a change of variable technique. We show that the VB can be directly modeled from the regression model of thermal dynamics without estimating the exact thermal parameters and heat disturbances. Third, aggregation of the VB models is implemented. The energy limits of aggregate VB models are designed considering the baseline load prediction error caused by disturbance uncertainty. Finally, simulation results verify the accuracy and effectiveness of the proposed VB modeling strategy.
Funder
Korea Electrotechnology Research Institute
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献