Abstract
This paper evaluates the influence of frequency-dependent soil conductivity and permittivity in the transient responses of single- and double-circuit transmission lines including the ground wires subjected to lightning strikes. We use Nakagawa’s approach to compute the ground-return impedance and admittance matrices where the frequency-dependent soil is modeled using Alípio and Visacro’s model. We compare some elements of these matrices with those calculated by Carson’s approach which assumes the frequency constant. Results show that a significant difference can be obtained in high resistive soils for these elements in impedance and admittance matrices. Then, we compute the transient responses for single- and double-circuit lines with ground wires located above soils of 500, 1000, 5000, and 10,000 Ω·m considering the frequency constant and frequency-dependent parameters generated for two lightning strikes (subsequent stroke and Gaussian pulse). We demonstrate that the inclusion of frequency dependence of soil results in an expressive reduction of approximately 26.15% and 42.75% in the generated voltage peaks in single- and double-circuit lines located above a high-resistive soil. These results show the impact of the frequency-dependent soils that must be considered for a precise transient analysis in power systems.
Funder
Fundação de Amparo à Pesquisa do Estado de São Paulo
Coordenação de Aperfeiçoamento de Pessoal de Nível Superior
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
6 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献