Abstract
In view of the difficulties in coordination between reliability and sensitivity of conventional generator differential protection, this paper presents a novel generator differential protection scheme based on a new braking method. On the basis of the mathematical model of the field-circuit coupling method and the electrical network cascade characteristics, the stator windings were combined and decoupled by the improved six-sequence component method to eliminate electromagnetic coupling between winding coils. In accordance with the basic characteristics of longitudinal impedance, the function of sub-item discrimination was realized. Numerous simulations and the up-to-date dynamic experiments showed that the proposed method has good state discrimination ability and can effectively resist the influence of current transformer saturation. Thus, it has an excellent prospect for engineering promotion.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献