Abstract
This work highlights the performance metrics and the fundamental degradation mechanisms of lead-acid battery technology and maps these mechanisms to generic duty cycles for peak shaving and frequency regulation grid services. Four valve regulated lead acid batteries have been tested for two peak shaving cycles at different discharge rates and two frequency regulation duty cycles at different SOC ranges. Reference performance and pulse resistance tests are done periodically to evaluate battery degradation over time. The results of the studies are expected to provide a valuable understanding of lead acid battery technology suitability for grid energy storage applications.
Funder
US Department of Energy, Office of Electricity
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)