Abstract
This paper presents an analysis of the short-circuit currents of a synchronous generator with a rated power of 16 kVA. For this purpose, the authors carried out measurements of real short-circuit currents during laboratory tests. Additionally, a simulation model of the generator was developed according to the individual machines data from the catalog and field calculations in ANSYS Maxwell software. Based on the mentioned research, the authors compared waveforms of the symmetrical short-circuit currents. In this paper, the last compared family of short-circuit current waveforms was obtained using analytic calculations. As the presented comparison shows, the assumed method of selecting short-circuit waveforms impacted their values. However, the difference in energy related to short-circuit currents did not influence on the selection of the short-circuit protections, especially at low values of steady-state short-circuit currents and short time constants characteristic for the generators, performing the functions of an alternative power supply. Regardless of the research method, the results presented in the article show that the selection of the short-circuit protections is complicated in case of hybrid electrical systems equipped with low power generators.