The paper reports the results of a comparative assessment concerned with the effectiveness of identifying the basic forms of partial discharges (PD) measured by the acoustic emission technique (AE), carried out by application of selected machine learning methods. As part of the re-search, the identification involved AE signals registered in laboratory conditions for eight basic classes of PDs that occur in paper-oil insulation systems of high-voltage power equipment. On the basis of acoustic signals emitted by PDs and by application of the frequency descriptor that took the form of a signal power density spectrum (PSD), the assessment involved the possibility of identifying individual types of PD by the analyzed classification algorithms. As part of the research, the results obtained with the use of five independent classification mechanisms were analyzed, namely: k-Nearest Neighbors method (kNN), Naive Bayes Classification, Support Vector Machine (SVM), Random Forests and Probabilistic Neural Network (PNN). The best results were achieved using the SVM classification tuned with polynomial core, which obtained 100% accuracy. Similar results were achieved with the kNN classifier. Random Forests and Naïve Bayes obtained high accuracy over 97%. Throughout the study, identification algorithms with the highest effectiveness in identifying specific forms of PD were established.