Author:
Zhou Xiaojie,Xu Dezhi,Huang Yourui
Abstract
This study addresses the output impedance model of the LCL-type grid-connected converter considering the dead-time effects and the digital control delay. The model shows that the digital control delay will affect the accuracy of the output impedance of the grid-connected converter, and the dead-time effects are only equivalent to superimposing a disturbance voltage on the original output impedance model. The derived output impedance model is verified by comparing it with the switching model in the PSIM simulation environment. The harmonic interaction between converter cluster and utility grid is modeled and analyzed based on the output impedance model. A combined harmonic suppression strategy is incorporated into every converter control scheme to suppress the harmonic interaction. Simulation results are presented to demonstrate the correctness of harmonic interaction analysis and the effectiveness of the proposed suppression strategy.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Cited by
3 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献