Author:
Leski Krystian,Luty Przemysław,Gwadera Monika,Larwa Barbara
Abstract
In this work, numerical simulation calculations were performed to investigate the minimum ground temperature that occurs when extracting thermal energy in a horizontal ground heat exchanger system in the Central European climate. The influence of ground thermal conductivity, heat flux extracted from the ground, periodic interruptions in the operation of the heat exchanger, periodic supply of heat energy to the ground, relative humidity of the ambient air, evaporation rate coefficient, and convective heat transfer coefficient on the ground minimum temperature were investigated. Based on the simulation, it was found that the high value of ground thermal conductivity favorably affects the operation of the installation with a ground heat exchanger. Both the reduction of the maximum heat flux taken from the ground, as well as periodic interruptions in the operation of the exchanger effectively protects the ground against excessive cooling. Further, it was found that heat supply to the ground in summer only slightly raises its minimum temperature, as well as the decrease of the relative humidity of the ambient air and evaporation rate coefficient. The change of the convective heat transfer coefficient has no significant impact on the minimum annual ground temperature.
Funder
Ministerstwo Nauki i Szkolnictwa Wyższego
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)