A high proportion of renewable energy connected to the power grid has caused power quality problems. Voltage-sensitive loads are extremely susceptible to voltage fluctuations, causing power system safety issues and economic losses. Considering the uncertainty factor and the time-varying characteristic, a linearized random ZIP model (constant impedance (Z), constant current (I), and constant power (P)) with time-varying characteristics was proposed. In order to improve the voltage quality of the voltage-sensitive loads in the day-here stage in an active distribution network (ADN), a linearized two-stage active and reactive power coordinated stochastic optimization model was established. The day-ahead active and reactive power coordination optimization was to smooth the large voltage fluctuation and develop a reserve plan to eliminate the unbalanced power caused by the prediction error in the day-here optimization. In the day-here real-time redispatch, the voltage was further improved by the continuous reactive power compensation device. Finally, the simulation results on the IEEE-33 bus system showed that the control strategy could better eliminate the unbalanced power caused by the prediction error and obviously improve the voltage of sensitive loads in the real-time stage on the premise of maintaining economic optimality.