Abstract
The load frequency control of a microgrid is one of the emerging areas due to the changes in demand and supply in power system. So the controllers’ implementation must be changed accordingly. This paper proposes an interval type-2 fuzzy logic-based, dual-mode gain scheduling (DMGS) of the proportional and integral controller in which the gains of the PI controller werescheduled through the dynamic selector. This proposed controller was implemented ina hybrid microgrid power system in which nonconventional energy sources wereadded to each area of the conventional power plant, which madethe system much more prone to frequency variations. The controller was designed for three areas, consisting of a photovoltaic (PV) system, a wind power system, a fuel cell and a diesel engine/hydropower generator in which the generation rate constraint (GRC) was considered as a nonlinearity. The proposed power system was investigated under various load conditions in the MATLAB/SIMULINK environment. A comparative evaluation of changes in frequency, tie-line power fluctuations and variations in area control errors for the test system showed the effectiveness of the current approach over simple fuzzy PI and a conventional PI-controlling approach.
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
4 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献