Abstract
The high amplitude and steep overvoltage generated by the breaking of the vacuum circuit breaker in the wind farm damages the inter-turn insulation of the transformer. There is a certain difference between the simulation results of the traditional reignition model and the measured overvoltage. It is necessary to improve the simulation model to simulate the overvoltage condition of the transformer more accurately and then select appropriate overvoltage protection measures. In this paper, based on the physical process of dielectric recovery during the opening process of the vacuum circuit breaker, a model of dielectric strength recovery is built to simulate the arc reignition of the vacuum circuit breaker. The model was applied to compare the overvoltage protection effects of RC snubbers, surge arresters, and choke coils. The simulation results show that the overvoltage amplitude and reignition times calculated by the model proposed in this paper are closer to the measured values. Compared with the traditional linear curve reignition model, the accuracy was increased by 24% and 51.2%, respectively. The parameter value of RC snubbers, the connection mode of surge arresters, and the combination mode of choke coil have an influence on overvoltage suppression. Finally, a suitable suppression scheme is proposed by installing a combined arrester on the high-voltage side of the transformer and connecting a choke coil in series, which can limit the phase-to-ground voltage and the phase-to-phase voltage to 2.43 p.u and 3.24 p.u, respectively, and reduce the steepness from 157.2 kV/μs to 22.3 kV/μs.
Funder
National Natural Science Foundation of China
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous),Building and Construction
Reference28 articles.
1. General Analysis of Vacuum Circuit Breaker Switching Overvoltages in Offshore Wind Farms;Ghafourian;IEEE Trans. Power Deliv.,2016
2. Effects of high frequency modeling & grounding system parameters on transient recovery voltage across vacuum circuit breakers for capacitor switching in wind power plants;Kafshgari;Int. J. Electr. Power Energy Syst.,2019
3. Abubakar, U., Mekhilef, S., Mokhlis, H., Seyedmahmoudian, M., Horan, B., Stojcevski, A., Bassi, H., and Rawa, M.J.H. (2018). Transient Faults in Wind Energy Conversion Systems: Analysis, Modelling Methodologies and Remedies. Energies, 11.
4. Reignition overvoltages induced by vacuum circuit breakers and its suppression in offshore wind farms;Guo;Int. J. Electr. Power Energy Syst.,2020
5. Wang, J., Geng, Y., and Liu, Z. (2017). The Theory and Technology of Single-Break Vacuum Circuit Breaker for Transmission Level, Machinery Industry Press.