Distributed Vibration Monitoring System for 10 kV-400 kVA 3D Wound Core Transformer under Progressive Short-Circuit Impulses

Author:

Tao Jiagui1,Zhang Sicong1,Dai Jianzhuo1,Zhu Jinwei1,Zhao Heng1

Affiliation:

1. Electrical Power Academy of Sciences, State Grid of Jiangsu Electric Power Co., Ltd., Nanjing 210024, China

Abstract

As large-scale, high-proportion, and efficient distribution transformers surge into the grids, anti-short circuit capability testing of transformer windings in efficient distribution seems necessary and prominent. To deeply explore the influence of progressively short-circuit shock impulses on the core winding deformation of efficient power transformers, a finite element theoretical model was built by referring to a three-phase three-winding 3D wound core transformer with a model of S20-MRL-400/10-NX2. The distributions of internal equivalent force and total deformation of the 3D wound core transformer along different paths under progressively short-circuit shock impulses varying from 60% to 120% were investigated. Results show that the equivalent stress and total deformation change rate reach their maximum as the short-circuit current increases from 60% to 80%, and the maximum and average variation rate for the equivalent stress reach 177.75% and 177.43%, while the maximum and average variation rate for the total deformation corresponds to 178.30% and 177.45%, respectively. Meanwhile, the maximum equivalent stress and maximum total deformation reach 29.81 MPa and 38.70 μm, respectively, as the applied short-circuit current increased to 120%. In light of the above observations, the optimization and deployment of wireless sensor nodes was suggested. Therefore, a distributed monitoring system was developed for acquiring the vibration status of the windings in a 3D wound core transformer, which is a beneficial supplement to the traditional short-circuit reactance detection methods for an efficient grid access spot-check of distribution transformers.

Funder

State Grid of Jiangsu Electric Power Co., Ltd

Publisher

MDPI AG

Reference36 articles.

1. Calculation of distribution loss under three-phase unbalance based on current phase estimation;Sun;Electr. Power Eng. Technol.,2020

2. Design and optimization for application performance of linear phase-shifting transformer;Zhang;Electr. Power Eng. Technol.,2022

3. Statistics and analysis on power transformer damage caused by short-circuit fault in 110kV and higher voltage class;Jin;Power Syst. Technol.,1999

4. The electromagnetic vibration characteristics of the first end of single-phase transformer;Pan;Electr. Power Eng. Technol.,2019

5. Status and progress of research on transformer vibration characteristics with DC bias;Li;Electr. Power Autom. Equip.,2018