The Effect of Airflow Velocity through a Laminar Airflow Ceiling (LAFC) on the Assessment of Thermal Comfort in the Operating Room

Author:

Mičko Pavol1ORCID,Nosek Radovan1ORCID,Hrabovský Peter1,Hečko Dávid1

Affiliation:

1. Research Centre, University of Zilina, Univerzitna 1, 01026 Zilina, Slovakia

Abstract

Forced ventilation is applied in clean rooms, specifically operating rooms, to ensure the health of both the patient and the medical staff. Ventilation reduces the risk of patient contamination, and its parameters are legally prescribed. In addition to preventing contamination, the ventilation system also ensures the creation of a comfortable environment for personnel who spend a large amount of working time in the operating room. This research focuses on the appropriate design of the air flow rate from the distribution element to the operating room. The PMV and PPD indexes were used to evaluate thermal comfort for human beings. The measurements of parameters determining thermal comfort took place in a laboratory with an accurate model of the operating room, including equipment and HVAC system, during the summer months, in cooling mode. Discharge speeds in the range of 0.15–0.175 m/s were evaluated as the most comfortable, with the PPD index ranging up to 22%. There was a significant increase in user dissatisfaction up to the limit of 70% at higher discharge speeds.

Publisher

MDPI AG

Subject

Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science

Reference46 articles.

1. (2015). Cleanrooms and Associated Controlled Environments-Part 1: Classification of Air Cleanliness by Particle Concentration. Standard No. EN ISO 14644-1.

2. (2023, February 20). Vyhláška č. 259/2008 Z. z., Vyhláška Ministerstva Zdravotníctva Slovenskej Republiky o Podrobnostiach o Požiadavkách na Vnútorné Prostredie Budov a o Minimálnych Požiadavkách na Byty Nižšieho Štandardu a na Ubytovacie Zariadenia. Available online: https://www.epi.sk/zz/2008-259.

3. (2020). Thermal Environmental Conditions for Human Occupancy. Standard No. ASHRAE Standard 55-2020.

4. (2008). Indoor Environmental Input Parameters for Design and Assessment of Energy Performance of Buildings Addressing Indoor Air Quality, Thermal Environment, Lighting and Acoustics. Standard No. EN ISO 15251.

5. Walenkamp, G.H.I.M. (2005). Beheersplan Luchtbehandeling Voor de Operatieafdeling, Werkgroep Infectiepreventie.

Cited by 1 articles. 订阅此论文施引文献 订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3