Abstract
This study investigates Smart Grid Optimised Buildings (SGOBs) which can respond to real-time electricity prices by utilising battery storage systems (BSS). Different building design characteristics are assessed to evaluate the impact on energy use, the interaction with the battery, and potential for peak load shifting. Two extreme cases based on minimum and maximum annual energy consumption were selected for further investigation to assess their capability of utilising BSS to perform arbitrage, under real-time pricing. Three operational dispatch strategies were modelled to allow buildings to provide such services. The most energy-efficient building was capable of shifting a higher percentage of its peak loads and export more electricity, when this is allowed. When using the biggest battery (220 kWh) to only meet the building loads, the energy-efficient building was able to shift 39.68% of its original peak loads in comparison to the 33.95% of the least efficient building. With exports allowed, the shifting percentages went down to 31.76% and 29.46%, respectively, while exports of 18.08 and 16.34 kWh/m2 took place. The formation of a regulatory framework is vital in order to establish proper motives for buildings to undertake an active role in the smart grid.
Subject
Building and Construction,Civil and Structural Engineering,Architecture
Cited by
1 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献