CO2 Concentration Assessment for Infection Monitoring and Occupancy Analysis in Tanzanian COVID-19 Isolation Centers

Author:

Karumuna Benson Vedasto123ORCID,Hao Long12

Affiliation:

1. Faculty of Architecture and Urban Planning, Chongqing University, Shapingba District, Chongqing 400045, China

2. Key Laboratory of the Ministry of Education of Mountainous City and Towns Construction and New Technology, Chongqing University, Shapingba District, Chongqing 400045, China

3. College of Architecture and Construction Technology, Mbeya University of Science and Technology, Mbeya P.O. Box 131, Tanzania

Abstract

Monitoring of IAQ is one of the foundations of the preventative actions prompted by the worldwide recognition of COVID-19 transmission. The measurement of CO2 has emerged as one of the most popular, dependable, and easy ways to indirectly evaluate the state of indoor air renewal. Reducing the risk of respiratory diseases transmitted by aerosols is attainable through implementing and validating prevention measures made possible by CO2 control. Isolation centers are like health facilities in that they are linked to IAQ, and the presence of natural ventilation can significantly improve the circulation of fresh air, which speeds up the removal of contaminants. This is true even though healthcare facilities are among the environments with the highest rate of COVID-19 propagation. Our investigation revealed, however, that no substantial critical data on air quality in Tanzanian isolation centers is presently available. The process of metabolic CO₂ creation and accumulation within health isolation center cubicles was investigated in this study. Crucially, we suggest comparing settings under various conditions using the indicator ppm/patient. In this research, we experimentally assessed the value of changing a few HVAC system characteristics. We looked at the data to see how well the filtration system worked concerning the submicron particle concentration. Study recommendations for CO2 detectors and ways to reduce infection risk in shared isolation center cubicles are provided. We also show the correlation between particle size and CO2 concentration, the correlation between CO2 concentration derivatives and air volume presented per patient in isolation cubicles, the correlation between patient occupancy and CO2 concentration levels in isolation cubicles, and how to improve air quality by adjusting the patient’s bed position. The study also found that for exposure lengths of two to three hours, a typical hospital cubicle with fifty to one hundred people should have an average interior CO₂ value of less than 900 ppm. Carers’ length of stay in the hospital substantially impacted the permissible CO2 concentration. By establishing a connection between indoor air monitoring and healthcare goals, this study will aid in determining the feasibility of establishing regulations for interior CO2 content depending on occupancy settings, strengthening preventive efforts against COVID-19. In the post-pandemic era, it will be essential to find ways to make health facilities air cleaner so that infectious diseases cannot spread in the future.

Funder

The National Natural Science Foundation of China

Publisher

MDPI AG

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370