Abstract
It has been challenging for designers to identify the appropriate design parameters that would reduce building energy consumption while achieving thermal comfort for building occupants. This study aims to determine the most important architectural building design parameters (ABDPs) that can increase thermal comfort and reduce energy use in educational buildings. The effect of 15 ABDPs in an Australian educational lecture theatre and their variabilities on energy consumption and students’ thermal comfort for each parameter were analysed using Monte Carlo (MC) techniques. Two thousand simulations for every input parameter were performed based on the selected distribution using the Latin hypercube sampling (LHS) technique. Sensitivity analyses (SA) and uncertainty analyses (UA) were used to assess the most important ABDPs in terms of thermal discomfort hours and energy consumption. The study found that the ABDPs, such as cooling set-point temperatures and roof construction, significantly reduce the operative temperature by up to 14.2% and 20.0%, respectively. Consequently, these reductions could significantly shorten the thermal discomfort hours, thereby reducing energy consumption by 43.7% and 41.0%, respectively. The findings of this study enable building designers to identify which ABDPs have a substantial impact on thermal comfort and energy consumption.
Subject
Building and Construction,Civil and Structural Engineering,Architecture
Cited by
35 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献