Numerical Analysis of Steam Ejector Performance with Non-Equilibrium Condensation for Refrigeration Applications

Author:

Lei Yu1,Li Shengyu2ORCID,Lu Jun2ORCID,Xu Ye1,Yong Yong1,Xing Dingding3

Affiliation:

1. Chongqing Airport Group Co., Ltd., Chongqing 401120, China

2. School of Civil Engineering, Chongqing University, Chongqing 400045, China

3. Chongqing Jida Environmental Engineering Technology Research Institute Co., Ltd., Chongqing 405299, China

Abstract

In recent years, there has been great interest in developing cooling systems with humidity- and temperature-independent control capabilities that can operate efficiently at varying temperatures. This paper proposes a bi-loop double-evaporator ejection–compression cycle, which utilizes low-grade heat and is suitable for the construction industry. The proposed cycle involves the concurrent operation of a vapor compression cycle and an ejector refrigeration cycle that enables it to handle altered pressure levels and operate with varying compression ratios all the way to a common condenser pressure. Conventional computational fluid dynamics (CFD) approaches often model steam as an ideal gas with single-phase flow. In contrast, this research employs the wet steam model to optimize ejector geometry. The wet steam model takes into account non-equilibrium water vapor condensation, thus providing a more precise assessment of spontaneous condensation behavior and its impact on ejector performance. When compared to the conventional dry gas model, the use of the wet steam model dramatically decreases the entrainment ratio error from 16.24% for single-phase steam to 3.92% when compared to experimental data. This study concentrates on four critical attributes of wet steam, including Mach number, droplet nucleation rate, average droplet radius, and liquid mass fraction, to develop a strategy for enhancing ejector performance and efficiency. The study demonstrates that optimal area and primary nozzle diameter ratios for the steam ejector are 5 and 2.4, respectively. Increasing the area ratio mitigates condensation intensity, thereby reducing the liquid mass fraction in the diffuser. Overall, this paper provides valuable insights into improving and optimizing ejector performance, thus highlighting the importance of considering the behavior of spontaneous condensation in ejector design and modeling.

Publisher

MDPI AG

Subject

Building and Construction,Civil and Structural Engineering,Architecture

同舟云学术

1.学者识别学者识别

2.学术分析学术分析

3.人才评估人才评估

"同舟云学术"是以全球学者为主线,采集、加工和组织学术论文而形成的新型学术文献查询和分析系统,可以对全球学者进行文献检索和人才价值评估。用户可以通过关注某些学科领域的顶尖人物而持续追踪该领域的学科进展和研究前沿。经过近期的数据扩容,当前同舟云学术共收录了国内外主流学术期刊6万余种,收集的期刊论文及会议论文总量共计约1.5亿篇,并以每天添加12000余篇中外论文的速度递增。我们也可以为用户提供个性化、定制化的学者数据。欢迎来电咨询!咨询电话:010-8811{复制后删除}0370

www.globalauthorid.com

TOP

Copyright © 2019-2024 北京同舟云网络信息技术有限公司
京公网安备11010802033243号  京ICP备18003416号-3