Abstract
A DC circuit breaker is piece of core equipment for DC grid construction and can achieve fast isolation of DC faults in the grid. In this paper, based on the fault characteristics and protection requirements of an AC/DC hybrid distribution network, the technical parameters and topology structure of an inductance and capacitance (LC) resonant commutation-type mechanical DC breaker are proposed. Furthermore, an engineering prototype of the mechanical DC circuit breaker is developed, then a small current breaking test and a large current breaking test are carried out. The test results show that a 10 kA fault current can be interrupted within 10 ms by the engineering prototype. Finally, the engineering prototype of the mechanical DC circuit breaker is installed in the AC/DC hybrid distribution network project, and a current breaking test is carried out. The test results show that the mechanical DC circuit breaker has good running conditions, and the function and performance meet the engineering design and operation requirements.
Funder
National Key Research and Development Program
Science and Technology Program of China Southern Power Grid
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
9 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献