Abstract
Power transformers are considered to be the most important assets in power substations. Thus, their maintenance is important to ensure the reliability of the power transmission and distribution system. One of the most commonly used methods for managing the maintenance and establishing the health status of power transformers is dissolved gas analysis (DGA). The presence of acetylene in the DGA results may indicate arcing or high-temperature thermal faults in the transformer. In old transformers with an on-load tap-changer (OLTC), oil or gases can be filtered from the OLTC compartment to the transformer’s main tank. This paper presents a method for determining the transformer oil contamination from the OLTC gases in a group of power transformers for a distribution system operator (DSO) based on the application of the guides and the knowledge of experts. As a result, twenty-six out of the 175 transformers studied are defined as contaminated from the OLTC gases. In addition, this paper presents a methodology based on machine learning techniques that allows the system to determine the transformer oil contamination from the DGA results. The trained model achieves an accuracy of 99.76% in identifying oil contamination.
Subject
Fluid Flow and Transfer Processes,Computer Science Applications,Process Chemistry and Technology,General Engineering,Instrumentation,General Materials Science
Cited by
15 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献