Abstract
Reversal ventilation is one of prevention methods against fire hazard in underground mines, but it is not recommended for the mines where methane is present. The authors introduce the new method of reversal and by conducting numerical simulations they prove that it allows to keep methane at the acceptable level during miners escape. However, it requires connection between the subnetworks of the main ventilation fans. It was also shown, that by using the method some escape routes will be shortened. It is possible to apply this method in the mines where the fans and stoppings are fully controlled across the full range of their operating parameters. The findings are important for underground mines, as well as for surface facilities where air control or smoke control is managed by two or more fans.
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)