Author:
Qi Di,Zhao Chuangyao,Li Shixiong,Chen Ran,Li Angui
Abstract
Earth to air heat exchangers are widely utilized to cool or heat passive buildings for energy savings. They often need to deal with high humidity air conditions, especially in the greenhouse due to plant transpiration, and the condensation phenomenon is frequently observed during the cooling process. To evaluate the effect of humidity and condensation on thermal performance, a three dimensional computational fluid dynamic (3D-CFD) model was developed. The distribution of relative humidity in each pipe was investigated, and the impact of inlet air relative humidity on the integrated performance of the earth to air heat exchanger was discussed. The effects of inlet air temperature and volume flow rate were also analyzed. Moreover, the influence of the heat exchanger configurations on the performance of the air condensation was researched. The results indicated that condensation had few effects on the airflow distribution uniformity of the earth to air heat exchanger, while it acted observably on the thermal performance. In addition, humid air in a small diameter pipe tended to condense more easily. Humidity and condensation should be taken into consideration for the design of earth to air heat exchangers in greenhouses during engineering applications.
Funder
National Natural Science Foundation of China
Scientific Research Program funded by the Shaanxi Provincial Education Department
Subject
Energy (miscellaneous),Energy Engineering and Power Technology,Renewable Energy, Sustainability and the Environment,Electrical and Electronic Engineering,Control and Optimization,Engineering (miscellaneous)
Cited by
14 articles.
订阅此论文施引文献
订阅此论文施引文献,注册后可以免费订阅5篇论文的施引文献,订阅后可以查看论文全部施引文献